Terminal Identification Table:
AL800ADA - Power Supply Board
Terminal Legend Function/Description
L,G,N Connect120VACtotheseterminals:Ltohot,Ntoneutral.
-DC+ 24VDC@8ampinalarmnon-powerlimitedoutput.
ACFAIL
NO,C,NC
Form“C”drycontactsindicatethelossofAC,withACpresentterminalsmarked[NOandC]
areopen,[NCandC]areclosed.WhenlossofACoccursterminalsmarked[NOandC]are
closed,[NCandC]areopen.
ACLOCAL
NC,NO,C
Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,
withACpresentterminalsmarked[NOandC]areopen,[NCandC]areclosed.WhenlossofAC
occursterminalsmarked[NOandC]areclosed,[NCandC]areopen.
BATFAIL
NO,C,NC
Form“C”drycontactsindicatelowbatteryvoltageorlossofbatteryvoltage.Undernormal
conditionsterminalsmarked[NOandC]areopen,[NCandC]areclosed.Duringatrouble
conditionterminalsmarked[NOandC]areclosed,and[NCandC]areopen(Fig. 2, pg. 7).
+BAT- Stand-bybatteryinput(leadsprovided)(Fig. 2, pg. 7).
*Power Board Parameter Specifications:
• ACFailconditionwillreportapproximately30secondsafterlossofAC.Todelayreportfor2.5to3hourscut
jumperACDELAYonthePowerSupplyBoard(ACtroubleoutputdelayoption).IfthismodeisselectedthePower
SupplyBoardmustberesetbyremovingallpowertoitfor30seconds.
• Lowbatteryconditionwillreportatapproximately21VDC.
• Batterypresencedetectionwillreportwithin180secondsafterbatteryremainsundetected(missingorremoved).
Arestoredbatterywillreportwithin30seconds.
LED Diagnostics:
AL800ADA - Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normaloperatingcondition.
ON OFF LossofAC,Stand-bybatterysupplyingpower.
OFF ON NoDCoutput.
OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
AL842LGK - Logic Board
LED OFF ON BLINK (LONG)* BLINK (SHORT)**
ON Normal AlarmCondition TroubleCondition TroubleConditionMemory
ON Normal AlarmCondition TroubleCondition TroubleConditionMemory
OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory
OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory
Input1 Normal AlarmCondition TroubleCondition ---
Input2 Normal AlarmCondition TroubleCondition ---
Fault Normal AlarmCondition --- ---
* Indicatesexistingtroublecondition.Whenatroublecondition(open,shortorground)occursonaspecificoutput,the
correspondingredoutputLED,[OUT1-OUT4]willblink.ThecorrespondinggreeninputLEDwillblinkaswell.
**Indicatestroubleconditionmemory.Whenatroubleconditionrestores,theunitsredoutputLEDs[OUT1-OUT4]
willblinkwithashorteranddistinctlydifferentduration.ThegreeninputLEDswillbeoff(normalcondition).
ToresetthememorydepresstheresetbuttonlocatedontheAL842LGKlogicboard(Fig. 2c, pg. 7).
TheLED(s)willextinguish.
Note: Whenindicatingcircuitshaverestored,troublememoryresetisnotrequiredfornormaloperation.