Rev. 042010AL842ULADANAC Power ExtenderInstallation Guide(See Application Guide for additional information)Altronix Corp.140 58th St. Brooklyn, NY
- 10 - AL842ULADAAppendix A - UL Listed Compatible DevicesA.1 Four (4) Wire Smoke DetectorsTableA-1belowlistsfour(4)wiresmokedetectorscomp
AL842ULADA - 11 -A.1 Four (4) Wire Smoke Detectors (cont.)Smoke Detector/BaseDetector TypeMax StandbyCurrent (mA)AlarmCurrent (mA)SystemSensor4W
Altronixisnotresponsibleforanytypographicalerrors.14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056website:www.a
- 2 - AL842ULADAAgency Listings:• ULListedforControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuildi
AL842ULADA - 3 -Power Supply Specifications:AC Input:120VAC60Hz,5ampsuppliedbyamaximum15ampdedicatedbranchcircuit.Output:Four(4)regul
- 4 - AL842ULADAOutput Programming Selection Table:Outputs must be programmed independently (OUT1 - OUT4)Function Switch Positions DescriptionsON
AL842ULADA - 5 -Terminal Identification Table:AL842LGK - Logic Board Terminal Legend Function/DescriptionIN1+,IN1-IN2+,IN2-(Supervised)Theset
- 6 - AL842ULADATerminal Identification Table:AL800ADA - Power Supply BoardTerminal Legend Function/DescriptionL,G,N Connect120VACtotheset
AL842ULADA - 7 -Fig. 2Optional Hookup Diagram:Fig. 2bFig. 2a NC NO C NC C NO NC C NOAC LocalAC DELAYBAT FAIL AC FAILAC LEDVR1OUT1 OUT2 OU
- 8 - AL842ULADAOptional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to
AL842ULADA - 9 -Battery Calculation WorksheetUnitsarecapableofrecharging40AHbatterymax.Iftotalampere-hourrequiredexceeds40AH,decreas