AL400UL - 1 -
Overview:
The AL400UL power supply converts a 115VAC / 60Hz input to a 12VDC or 24VDC power-limited output
(see specifications). The AL400UL is UL Listed for fire alarm, burglar alarm, and access control applications.
Specifications:
Power Supply Voltage Output Selections:
Output Switch Position
12VDC SW1, 2 ON, SW3, 4 OFF
24VDC SW1, 2 OFF, SW3, 4 ON
Stand-by Specifications:
Output
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by = 4.0 amp
Alarm = 4.0 amp
Stand-by = 1.0 amp
Alarm = 4.0 amp
Stand-by = 300mA
Alarm = 4.0 amp
24VDC / 12AH Battery --------
Stand-by = 200mA
Alarm = 3.0 amp
--------
24VDC / 40AH Battery
Stand-by = 3.0 amp
Alarm = 3.0 amp
Stand-by = 1.0 amp
Alarm = 3.0 amp
Stand-by = 300mA
Alarm = 3.0 amp
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 4).
Secure enclosure to earth ground.
2. Set the AL400UL to the desired DC output voltage by setting dip switches (Fig. 1) to the appropriate position
(see Power Supply Voltage Output Specifications Chart).
3. Connect AC power (115VAC / 60Hz) to the black and white flying leads of the transformer(Fig. 1).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
AL400UL - UL Listed, Multi-Agency Approved
Power Supply/Charger
Altronix Corp.
140 58th St. Brooklyn, NY
Agency Listings:
• ULListed
Fire, Burglar and Access Control
Power Supply (UL1481, UL603, UL294).
• MEA-NYCDepartmentofBuildingsApproved.
• CSFM-CaliforniaStateFireMarshalApproved.
• NFPA72compliant
Input:
• Input115VAC,60Hz,3.5amp.
Output:
• 12VDC or 24VDC selectable output.
•12VDC@4ampor24VDC@3ampsupplycurrent.
• Class 2 Rated power-limited output.
• Filteredandelectronicallyregulatedoutput.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
•Batteryleadsincluded.
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Automaticswitchovertostand-bybatterywhenACfails.
• Maximumchargecurrent1.2amp.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
Visual Indicators:
• ACinputandDCoutputLEDindicators.
Enclosure Dimensions (H x W x D approx.):
12.25”x7.25”x4.5”(311.15mmx184.15mmx114.3mm)