- 6 - AL802ULADAJ
Terminal Identification Table:
AL800ADA Power Supply Board*
*Power Board Parameter Specifications:
• AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut
jumper AC DELAY on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power
Supply Board must be reset by removing all power to it for 30 seconds.
• Low battery condition will report at approximately 21VDC.
• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or removed).
A restored battery will report within 30 seconds.
LED Diagnostics:
AL800ADA - Power Supply Board
AL800LGK - Logic Board
Terminal
Legend
Function/Description
L, G, N
Connect 120 VAC to these terminals:
L to hot, N to neutral, G to ground.
+ DC – 24VDC @ 8 amp in alarm non-power limited output.
AC FAIL
NC, C, NO
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation
devices, with AC present terminals marked NO and C are open, NC and C are closed.
When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
AC LOCAL
NC, C, NO
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation
devices, with AC present terminals marked NO and C are open, NC and C are closed.
When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
BAT FAIL
NC, C, NO
Form “C” dry contacts used to signal low battery voltage or loss of battery voltage.
Under normal conditions terminals marked NO and C are open, NC and C are closed.
During a trouble condition terminals marked NO and C are closed, and NC and C
are open (Fig. 2, pg. 7).
+ BAT – Stand-by battery input (leads provided) (Fig. 2, pg. 7).
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
LED OFF ON BLINK (LONG)* BLINK (SHORT)**
ON Normal Alarm Condition Trouble Condition Trouble Condition Memory
ON Normal Alarm Condition Trouble Condition Trouble Condition Memory
OFF Normal Alarm Condition Trouble Condition Trouble Condition Memory
OFF Normal Alarm Condition Trouble Condition Trouble Condition Memory
Input 1 Normal Alarm Condition Trouble Condition ---
Input 2 Normal Alarm Condition Trouble Condition ---
Fault Normal Alarm Condition --- ---