LED Diagnostics:
OLS250/OLS257 - Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition
ON OFF Loss of AC, Stand-by battery supplying power
OFF ON No DC output
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
PD4/PD4CB/PD8/PD8CB - Power Distribution Module
Green Power Distribution Module Status
ON Normal operating condition.
Terminal Identification:
OLS250/OLS257 - Power Supply Board
Terminal Function/Description
Legend
L, G, N Connect 115VAC to these terminals:
L to Hot, N to Neutral, G to ground (if used).
+ DC - 24VDC @ 10 amp continuous outputs.
*AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm
N.O., C, N.C. panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 120VAC / 28VDC
*Low Battery Used to indicate low battery condition, e.g. connect to alarm panel.
N.O., C, N.C. Relay normally energized when DC power is present.
Contact rating 1 amp @ 120VAC / 28VDC
Low battery threshold:
24VDC output threshold set @ approximately 21VDC.
- BAT + Stand-by battery connections. Maximum charge rate .7 amp.
*Note: Supervised Models Only.
PD4/PD4CB/PD8/PD8CB - Power Distribution Module
Terminal Legend Function/
PD4/PD4CB PD8/PD8CB Description
1P to 4P 1P to 8P Positive DC power outputs.