ReServWP Outdoor Video Surveillance UPS units are designed to provide power for 24VAC and/or 12VDC cameras dur-
ing normal or power outage conditions. True sine wave regulated AC outputs and/or regulated DC outputs.
ReServWP Series Outdoor Video Surveillance UPS Configuration Reference Chart:
Altronix
Model Number
Output/Supply
Current (Amp
Ambient
Temperature
Input Rating
PTC Protected
Power-Limited
Outputs
24VAC Outputs
12VDC Outputs
Agency Listings
UL Listings and
File Numbers
ReServ1WP
24VAC @ 4 amp (100VA)
& 12VDC @ 2 amp
-33º - 30º C
115VAC 60Hz,
3.5 amp
16 12 4
UL File #
E329542
UL 60950-1
UL/CUL Listed
for
Information
Technology
Equipment.
24VAC @ 3.5 amp (85VA)
& 12VDC @ 2 amp
-33º - 42º C
ReServ2WP
24VAC @ 4 amp (100VA) -33º - 30º C
115VAC 60Hz,
3.5 amp
16 16 ----
24VAC @ 3.5 amp (85VA) -33º - 42º C
ReServ3WP 12VDC @ 8 amp -33º - 42º C
115VAC 60Hz,
3.5 amp
16 ---- 16
Specifications:
Stand-by Specifications:
ReServ1WP
Stand-by Batteries 4 amp (100VA) load at 24VAC and 2 amp load at 12VDC max.
Two (2) 12VDC/7AH 45 minutes
Two (2) 12VDC/12AH 90 minutes
ReServ2WP
Stand-by Batteries 4 amp (100VA) max. load at 24VAC
Two (2) 12VDC/7AH 45 minutes
Two (2) 12VDC/12AH 90 minutes
ReServ3WP
Stand-by Batteries 8 amp (100VA) max. load at 12VDC
Two (2) 12VDC/7AH 45 minutes
Two (2) 12VDC/12AH 90 minutes
Output:
• PTC protected power-limited outputs are rated @ 1 amp.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Automatic switchover to stand-by battery
when AC fails.
Supervision:
AC fail supervision (form “C” contacts).
Low battery supervision (form “C” contacts).
Visual & Audio Indicators:
AC/DC power LED indicators.
Individual power output LED indicators.
Low voltage input and Shutdown LED indicators.
Visual & Audio Indicators (cont’d):
Audio AC Fail and Battery Fail indicator.
Additional Features:
True sine wave regulated AC outputs (ReServ1WP &
ReServ2WP). Regulated DC outputs (ReServ1WP &
ReServ3WP).
Unit maintains camera synchronization.
Ease of installation saves time and eliminates costly labor.
Enclosure Dimensions:
NEMA4 / IP66 Rated enclosure.
Enclosure accommodates up to
two (2) 12VDC/7AH batteries.