Maximal1RD rack mount access power controller distributes and switches
power to access control systems and accessories. It converts a 115VAC
50/60Hz input into sixteen (16) independently controlled 12VDC or 24VDC
PTC protected outputs. Outputs are activated by an normally open (NO) or
normally closed (NC) dry trigger input from an Access Control System, Card
Reader, Keypad, Push Button, PIR, etc. This unit will route power to a variety
of access control hardware devices including: Mag Locks, Electric Strikes,
Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or
Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm
Monitoring, or may be used to trigger other auxiliary devices. The fire alarm
disconnect feature is individually selectable for any or all of the outputs.
Input:
• 115VAC60Hz.,1.9amp.
• Normallyclosed[NC]ornormallyopen[NO]
dry contact inputs (switch selectable).
Outputs:
• 12VDC@4ampor24VDC@3amp
total output current.
• Sixteen(16)PTCprotectedoutputs.
• MaximumcurrentperACM8R-Moutputis2amp.
• IndividuallyselectableMagLock/Strike(Fail-Safe,
Fail-Secure) solid state fuse protected outputs.
• Thermalandshortcircuitprotectionwithautoreset.
Fire Alarm Interface:
• LatchingorNon-Latchingfirealarmresetswitch
individually selectable for each output.
• RemoteresetcapabilityforlatchingFireAlarm
Interface mode.
• FireAlarmdisconnectinputoptions:
a)Normallyopen[NO]ornormallyclosed[NC]
dry contact input.
b) Polarity reversal input from FACP signaling
circuit.
Visual Indicators:
• IndividualOutputStatusLEDslocatedonthe
front panel.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltype
batteries (if batteries are required install
separate enclosure).
• Maximumchargecurrent.7amp.
• Automaticswitchovertostand-bybattery
when AC fails.
• Zerovoltagedropwhenunitswitchesovertobattery
backup (AC failure condition).
Supervision:
• ACfailsupervision(form“C”contact).
• Lowbatteryandbatterypresencesupervision
(form“C”contact).
Additional Features:
• Removableterminalblockswithlockingscrewflange.
• 3-wirelinecord.
• Illuminatedmasterpowerdisconnectcircuitbreaker
with manual reset.
Mechanical:
• Dimensions(HxWxD)(approx.):3.25”(82.55mm)x
19.125”(485.78mm)x8.5”(215.9mm)
• Shipping Weight (approximate):12.7lbs(5.76kg).
Maximal1RD
Rack Mount Access Power Controller
Rev.DSMaximal1RD-10312012
Overview
Specifications
Maximal1RD
Kommentare zu diesen Handbüchern