Overview:
SMP7 power supply/charger converts low voltage AC input into 12VDC or 24VDC @ 6 amp of continuous supply
current (refer to specifications). This general purpose power supply has a wide range of applications for access control,
security and CCTV system accessories that require additional power.
Specifications:
Input:
28VAC/175VA.
Output:
12VDC or 24VDC selectable output.
6 amp continuous supply current.
Filtered and electronically regulated output.
Thermal overload and short circuit protection.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 600mA.
Automatic switch over to stand-by battery when AC fails.
Additional Featur
es:
AC input and DC output LED indicators.
Includes batter
y leads.
Board Dimensions (approximate): 7”L x 4.25”W x 1.75”H
* Specified at 25˚ C ambient.
Voltage Output/T
ransformer Selection Table:
Output VDC Switch Position Max. Load DC Transformer Requirements
(Recommended Altr
onix Part #’s)
12VDC
SW 1 Closed 6 amp 24VAC or 28VAC / 175VA ( T2428175)
24VDC SW1 Open 6 amp 24VAC or 28VAC / 175VA ( T2428175)
Installation Instructions:
The SMP7 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the SMP7 in desired location/enclosure.
2. Set the SMP7 to the desired DC output voltage by setting the switches to the appropriate positions
(
r
ef
er to
V
olta
g
e Output/Transformer Selection Table
).
3. Connect proper transformer to terminals marked [AC] (
refer Voltage Output/Transformer Selection Table).
Use 18 AWG or larger for all power connections (Battery, DC output).
4.
Measure output v
oltage before connecting devices. This helps avoid potential damage.
5. Connect devices to be powered to terminals marked [+ DC -].
6. When the use of stand-by batteries are desired, they must be lead
acid or gel type. Connect battery to terminals marked [+ BAT -].
(battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used a loss of
A
C will result in the loss of output voltage.
LED Diagnostics:
Red (DC)
Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
SMP7 - Power Supply/Charger
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - SMP7 - Power Supply/Charger

Overview:SMP7 power supply/charger converts low voltage AC input into 12VDC or 24VDC @ 6 amp of continuous supply current (refer to specifications). T

Seite 2 - OPEN = 24V SW1 CLOSED = 12V

Terminal Identification:Terminal Function/DescriptionLegendAC/AC Low voltage AC input (28VAC / 175VA). Altronix model # T2428175+ DC -- 12VDC or 24VDC

Kommentare zu diesen Handbüchern

Keine Kommentare