Overview:
LPS3/LPS3R linear power supply/chargers will convert a low voltage AC input to a low voltage 12VDC/24VDC output.
These power supplies are specifically designed to provide to power needed by the most demanding security and access
control applications.
Specifications:
Input:
16VAC or 28VAC
(
refer to voltage output/transformer selection chart).
Output:
12VDC/24VDC selectable output.
2.5 amp continuous supply current.
Filtered and electronically regulated output.
Thermal overload and short circuit protection.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 500mA.
Automatic switch over to stand-by battery.
Fused battery protection (circuit breaker available).
Includes battery leads.
Visual Indicators:
AC input and DC output LED indicators.
Board Dimensions (approximate):
6.5”L x 3.5”W x 1.75”H
Specified at 25˚ C ambient.
Voltage Output/Transformer Selection Table:
Output Voltage Switch Transformer Requirements
Position (Recommended Altronix Part #’s)
12VDC Closed 16VAC / 56 VA (T1656).
24VDC
Open
24VAC or 28VAC / 100VA
(Altronix model T2428100)
Note: Transformers with higher VA ratings may be used.
Installation Instructions:
The LPS3/LPS3R should be installed in accordance with The National Electrical Code and all applicable Local
Re
gulations.
1.
Mount the LPS3/LPS3R in desired location / enclosure.
2. Set DC output voltage using switch SW2
(refer to voltage output/transformer selection table).
3. Connect proper transformer to terminals marked AC
(refer to voltage output/transformer selection table).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect devices to be powered to terminals marked [ --- - DC +].
6. When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect battery to terminals marked [+ BAT --- ] on the unit (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
7. When batteries are not used a loss of AC will result in the loss of output voltage.
8.
Connect super
visor
y trouble reporting devices to outputs marked [AC Fail] (LPS3R only).
LPS3/LPS3R - Linear Power Supply/Charger
A
C
D
C
AC
AC FAIL
C
ONTACTS
AC
-- DC +
-- BAT +
NC C NO
SW1
1
2V-CLOSED
24V-OPEN
Supervision:
LPS3R is the same as LPS3 w/ AC Fail
supervision (Form “C” contacts.)
OPEN SWITCH
CLOSED SWITCH
Switch Detail
AC
DC
AC
AC FAIL
CONTACTS
AC
-- DC +
-- BAT +
NC C NO
SW1
12V-CLOSED
24V-OPEN
Fig. 1
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - -- BAT +

Overview:LPS3/LPS3R linear power supply/chargers will convert a low voltage AC input to a low voltage 12VDC/24VDC output. These power supplies are spe

Seite 2 - LED Diagnostics:

LED Diagnostics:Red (DC) Green (AC) Power Supply StatusON ON Normal operating condition.ON OFF Loss of AC, Stand-by battery supplying power.OFF ON No

Kommentare zu diesen Handbüchern

Keine Kommentare