Overview:
LPS3AC linear power supply/charger will convert a low voltage AC input to a 12VDC/24VDC output. This power supply
is specifically designed to provide the power needed by the most demanding security and access control applications.
Specifications:
Input:
• 16VAC or 28VAC (refer to Voltage Output/Transformer Selection Chart).
Output:
• 12VDC/24VDC selectable output.
• 2.5 amp continuous supply current.
• Filtered and electronically regulated output.
• Thermal overload and short circuit protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
•
Maximum charge current 500mA.
• Automatic switch over to stand-by battery.
• Fused battery protection (circuit breaker available).
• Includes battery leads.
Supervision:
• Provides AC Fail supervision (Form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators.
Board Dimensions (approximate):
6.5”L x 3.5”W x 1.75”H
Specified at 25˚ C ambient.
Voltage Output/Transformer Selection Table:
Output
Voltag
e Switch Transformer Requirements
Position (Recommended Altronix Part #’s)
12VDC Closed 16VAC / 56 VA (T1656).
24VDC
Open
24VAC or 28VAC / 100VA
(Altronix model
T2428100)
Note: Transformers with higher VA ratings may be used.
Installation Instr
uctions:
The LPS3AC should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the LPS3AC in desired location / enclosure.
2. Set DC output voltage using switch SW2
(Fig. 1) (refer to Voltage Output/Transformer Selection Chart).
3. Connect proper transformer to terminals marked AC (refer to Voltage Output/Transformer Selection Chart).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect devices to be powered to terminals marked [ --- - DC +].
6.
When the use of stand-by batteries are desired, they must be lead acid or gel type.
Connect batter
y to terminals marked [+ BAT --- ] on the unit (battery leads included).
Use tw
o (2) 12VDC batteries connected in series for 24VDC operation.
7. When batteries are not used a loss of AC will result in the loss of output voltage.
8. Connect supervisory trouble reporting devices to outputs marked [AC Fail].
LPS3AC - Linear Power Supply/Charger
OPEN SWITCH
CLOSED SWITCH
Switch Detail
AC
DC
AC
AC FAIL
CONTACTS
AC
-- DC +
-- BAT +
NC C NO
SW2
12V-CLOSED
24V-OPEN
Fig. 1