Input:
• 120VAC,60Hz,3.5amp.
• Inputfuse:5A/250V.
Output:
• 12VDCor24VDCselectableoutput.
•12VDCor24VDC@2.0ampsupplycurrent.
• Power-limitedoutput.
• AuxiliaryPower-limitedoutput
rated@1amp(unswitched).
• Ripplevoltage:960mV.
• OverVoltageProtection.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent1.54amp.
• Automaticswitchovertostand-bybatterywhen
ACfails.Transfertostand-bybatterypoweris
instantaneouswithnointerruption.
Supervision:
• ACfailsupervision(form“C”contacts).
• Batteryfail&presencesupervision
(form“C”contacts).
• Lowpowershutdown.ShutsdownDCoutputterminals
ifbatteryvoltagedropsbelow71-73%for12Vunits
and70-75%for24Vunits(dependingonthepower
supply).Preventsdeepbatterydischarge.
Fire Alarm Disconnect:
• SupervisedFireAlarmdisconnect(latchingor
non-latching)10KEOLresistor.Operatesona
normallyopen(NO)ornormallyclosed(NC)trigger.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• BTU/Hr.:
12VDC:12.28BTU/Hr.
24VDC:24.57BTU/Hr.
• SystemACinputVArequirement:420VA.
Visual Indicators:
• GreenACPowerLEDindicates120VACpresent.
• ACinput,DCoutputandBatteryLEDindicators.
Additional Features:
• Shortcircuitandoverloadprotection.
• Unitiscompletewithpowersupply,enclosure,
batteryleadsandcamlock.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm)
- Accommodatesuptotwo(2)12VDC/12AHbatteries.
• Productweight(approx.):11.7lbs.(5.31kg).
• Shippingweight(approx.):13.0lbs.(5.90kg).
Specifications
eFlow3NXisapowersupply/chargerthatconvertsa120VAC/60Hzinputintoasingle
12VDCor24VDCClass2Ratedpowerlimitedoutput.
eFlow3NX
Power Supply/Charger
Rev.DSeFlow3NX_10242013
Overview
Agency Approvals
UL294 ULListedforAccessControl
SystemUnits.
UL603 ULListedforPowerSupplies
forUsewithBurglar-Alarms
Systems.
UL1481 ULListedforPowerSupplies
forFireProtectiveSignaling
Systems.
eFlow3NX
ULC-S318-96 - Power Supplies for Burglar
AlarmSystems.AlsosuitableforAccessControl.
CSFM-CaliforniaStateFire
MarshalApproved.
Altronix Corp.
140 58th St. Brooklyn, NY
CE-EuropeanConformity
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Power Supply/Charger

Input:• 120VAC,60Hz,3.5amp.• Inputfuse:5A/250V.Output:• 12VDCor24VDCselectableoutput.•12VDCor24VDC@2.0ampsupplycurrent.• Power-l

Seite 2 - (H x W x D approximate):

Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.comEnclosure Dimensions (H x W x D approximate):15.5”x

Kommentare zu diesen Handbüchern

Keine Kommentare