Agency Listings:
• ULRecognizedcomponentfor:AccessControl
SystemUnits(UL294),PowerSupplies
forFireProtectiveSignalingSystems(UL1481).
Input:
• Input115VAC60Hz,3.5amp.
Output:
• 12VDCor24VDCselectablenonpower-limitedoutput.
• 6ampcontinuoussupplycurrent.
• Filteredandelectronicallyregulatedoutput.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent0.7amp.
Battery Backup (cont’d):
• Automaticswitchovertostand-bybatterywhenACfails.
• Zerovoltagedropwhenswitchedovertobatterybackup.
Visual Indicators:
• ACinput,DCoutputandBATtroubleLEDindicators.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatteryandbatterypresencesupervision
(form“C”contacts).
Additional Features:
• Shortcircuitandthermaloverloadprotection.
Board Dimensions (W x L x H approximate):
4.5”x7.8”x2.6”(114.3mmx198.12mmx66.04mm)
Power Supply Output Selections:
Output Switch Position
12VDC SW1-CLOSED(Fig. 1, on the right)
24VDC SW1-OPEN(Fig. 1, on the right)
Stand-by Specifications:
Output
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC/40AHBattery
Stand-by=6.0amp
Alarm=6.0amp
Stand-by=1.0amp
Alarm=6.0amp
Stand-by=300mA
Alarm=6.0amp
24VDC/12AHBattery
--------
Stand-by=200mA
Alarm=6.0amp
--------
24VDC/40AHBattery
Stand-by=6.0amp
Alarm=6.0amp
Stand-by=1.0amp
Alarm=6.0amp
Stand-by=300mA
Alarm=6.0amp
Installation Instructions:
TheAL600ULXBshouldbeinstalledinaccordancewitharticle760ofTheNationalElectricalCodeaswellasNFPA
72andallapplicableLocalCodes.
1. MounttheAL600ULXBinthedesiredlocation/enclosure.
2. SettheAL600ULXBtothedesiredDCoutputvoltagebysettingSW1(Fig. 1)totheappropriate
 position(refer to Power Supply Output Selections chart).
3. ConnectACpower(115VAC60Hz)totheterminalsmarked[L,G,N](Fig. 2).Use18AWGorlargerforall
 powerconnections(Battery,DCoutput,ACinput).
 Use22AWGto18AWGforpower-limitedcircuits(ACFail/LowBatteryreporting).
Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
4. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.
 Maximumripplevoltageratingis0.8V.
5. Connectdevicestobepoweredtotheterminalsmarked[+DC---](Fig. 2).
AL600ULXB
UL Recognized Power Supply/Charger
Overview:
TheAL600ULXBisapowersupply/chargerthatconvertsa115VAC60Hzinputintoa6amp,12VDCor24VDC
nonpower-limitedoutput(seespecifications).
Specifications:
+ DC ---
BAT FAIL
NC C NO NC C NO
+ BAT ---
AC FAIL
DCAC BAT
LG N
5A 250V
OPEN - 24V
CLOSED - 12V
Fig. 1
O PEN SWITCH
CLOSED SWITCH
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - AL600ULXB

Agency Listings:• ULRecognizedcomponentfor:AccessControl SystemUnits(UL294),PowerSupplies forFireProtectiveSignalingSystems(UL1481

Seite 2 - Terminal Identification:

6. ForAccessControlapplicationsbatteriesareoptional. WhenbatteriesarenotusedalossofACwillresultin thelossofoutputvoltage.