Specifications
Input:
• Input115VAC,60Hz,3.5amp.
• Inputfuserated@3.5amp/250V.
Output:
• 12VDCor24VDCselectableoutput.
BurglarAlarmApplications(UL603):
12VDC=11.5VDC-13VDC.
24VDC=23VDC-26VDC.
•12VDC@4ampor24VDC@3ampsupplycurrent.
• Class2Ratedpowerlimitedoutput.
• Filteredandelectronicallyregulatedoutput.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Built-inchargerforsealedleadacidor
geltypebatteries.
• Automaticswitchovertostand-bybattery
whenACfails.
• Maximumchargecurrent0.7amp.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
• Batterypresencesupervision(form“C”contacts).
Visual Indicators:
• ACinput,DCoutputandBatteryLEDindicators.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• BTU/Hr.:
12VDC:14.71-16.63BTU/Hr.
24VDC:29.43-32.41BTU/Hr.
• SystemACinputVArequirement:345VA.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
13.5”(342.9mm)x13”(330.2mm)x3.25”(82.55mm)
- Accommodatesuptotwo(2)12VDC/7AHbatteries.
• Productweight(approx.):8.65lbs.(3.86kg).
• Shippingweight(approx.):9.55lbs.(4.26kg).
AL400ULXisapowersupply/chargerthatconvertsa115VAC/60Hzinputinto
asingle12VDCor24VDCClass2Ratedpowerlimitedoutput.
AL400ULX
Power Supply/Charger
Rev.DSAL400ULX_12282012
Overview
Agency Approvals
UL294 ULListedforAccessControlSystemUnits.
UL603 ULListedStandardforPowerSuppliesforUsewithBurglar-AlarmSystems.
UL1069 ULListedHospitalSignalingandNurseCallEquipment.