Agency Approvals
Specifications
UL 294 UL Listed for Access Control
System Units.
UL 603 UL Listed Standard for Power
Supplies for Use with Burglar-
Alarm Systems.
UL 1069 UL Listed Hospital Signaling and
Nurse Call Equipment.
UL 1481 UL Listed Standard for Safety for
Fire Protective Signaling Systems.
Input:
• Input115VAC,60Hz,3.5amp.
• Inputfuserated@3.5amp/250V.
Output:
• 12VDCor24VDCselectableoutput.
Burglar Alarm Applications (UL 603):
12VDC=10VDC-13.2VDC.
24VDC=20VDC-26.4VDC.
•12VDCor24VDC@2.5ampsupplycurrent.
• Sixteen(16)Class 2 Rated fuse protected power
limited outputs.
• Outputsarerated@3.5amp.
• Filteredandelectronicallyregulatedoutputs.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Built-inchargerforsealedleadacidor
geltypebatteries.
• Automaticswitchovertostand-bybattery
when AC fails.
• Maximumchargecurrent0.7amp.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
• Batterypresencesupervision(form“C”contacts).
Visual Indicators:
• ACinput,DCoutputandBatteryLEDindicators.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• BTU/Hr.:
12VDC:14.71-16.63BTU/Hr.
24VDC:29.43-32.41BTU/Hr.
• SystemACinputVArequirement:345VA.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
15.5”(393.7mm)x12”(304.8mm)x4.5”(114.3mm)
- Accommodatesuptotwo(2)12VDC/12AHbatteries.
• Productweight(approx.):10.1lbs.(4.58kg).
• Shippingweight(approx.):11.4lbs.(5.17kg).
AL300ULXPD16R is a multi-output power supply/charger that converts a
115VAC/60Hzinputintosixteen(16)Class2Rated12VDCor24VDCpower
limited outputs.
AL300ULXPD16R
Multi-Output Power Supply/Charger
Rev.DSAL300ULXPD16R_12052012
Overview
AL300ULXPD16R