Overview:
The AL201ULB is a power limited power supply/charger that converts a 24VAC input, into a 12VDC output,
(see specifications). It is intended for use in applications requiring UL Listing for Access Control System
Units (UL 294).
Specifications:
• ULRecognizedcomponent.
• Class2Rated.
• 24VAC40VAinput.UseULListedplug-intransformer.
• 12VDCpowerlimitedoutput.
• 1.75ampcontinuoussupplycurrent@12VDC.
• Filteredandelectronicallyregulatedoutput.
• Maximumchargecurrent400mA.
• Automaticswitchovertostand-bybatterywhenACfails(zerovoltagedrop).
• ACfailsupervision(form“C”1amp@28VDC).
• Lowbatterysupervision(form“C”1amp@28VDC).
• ACinputandDCoutputLEDindicators.
• Shortcircuitandthermaloverloadprotection.
• Includespowersupplyandbatteryleads.
BoardDimensions(approximate):3”Hx5.75”Wx1.2”H
Power Supply Output Specifications:
Output VDC Max. Stand-by Load DC Max. Alarm Load DC Battery (optional)
12VDC 1.75amp 1.75amp 12VDC/7AH
Stand-by Specifications:
Output 4 hr. of Stand-by & 5 Minutes of Alarm
12VDC/7AHBattery Stand-by=1.25amp
Installation Instructions:
TheAL201ULBshouldbeinstalledinaccordancewitharticle760ofTheNationalElectricalCodeorNFPA72aswell
asallapplicableLocalCodes.
See Terminal Identification Chart on page 2 for a description of each terminal function.
1. MounttheAL201ULBindesiredlocation/enclosure.
2. Connect24VAC/40VAtransformertoterminalsmarked[XFMRINPUT].
Use18AWGorlargerforallpowerconnections(Battery,ACinput).Use22AWGto18AWGfor
powerlimitedcircuits(DCoutput,ACFAILandLOWBATsupervisoryrelays).
Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum .25” spacing must be provided.
3. Connectbatterytoterminals[+BAT--]asmarkedontheunit(batteryleadsincluded).
Note:ForAccessControlapplications,batteriesareoptional.WhenbatteriesarenotusedalossofACwillresult
inthelossofoutputvoltage.Whentheuseofstand-bybatteriesisdesired,theymustbeleadacidorgeltype.
4. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidpotentialdamage.
5. Connectdevicestobepoweredtoterminalsmarked[+DC--](Fig. 1).
6. ConnectappropriatesignalingnotificationdevicestoACFailandLowBatsupervisoryrelayoutputs.
Note:TomeetULrequirements,ACSupervisoryoutputsmustbeconnectedtothezoneofAlarm
ControlPanelortoavisualACtroubleindicator.
AL201ULB
Access Control Power Supply/Charger